Wire Gauge (AWG) Calculator

ft
A
Current vs Ampacity
Current Draw
Remaining Capacity
Max Ampacity
Load %
Voltage Drop
Voltage Drop %
Wire Resistance
Status

AWG Ampacity Guide

14 AWG = 15 A (lighting)  |  12 AWG = 20 A (outlets)  |  10 AWG = 30 A (dryer)  |  8 AWG = 40 A (range)  |  6 AWG = 55 A (AC unit). These are NEC values for copper wire in conduit at 60°C.

Voltage Drop

Voltage Drop = 2 × Length × Current × Resistance per foot. The factor of 2 accounts for both the hot and neutral conductors. NEC recommends keeping voltage drop under 3% for branch circuits and under 5% total to the load.

Choosing Wire Gauge

Always size wire for the breaker protecting the circuit, not just the load. A 20 A breaker requires minimum 12 AWG wire. For long runs (50+ ft), consider going one gauge larger to reduce voltage drop.